Pengaruh Penutupan-Balik Tak-Sinkron terhadap Generator Induksi 3-Fase dalam Skema Pembangkitan Tersebar

  • M. Isnaeni B. S. Universitas Gadjah Mada
  • F. Danang Wijaya Universitas Gadjah Mada
  • Eka Firmansyah Universitas Gadjah Mada
Keywords: PBTS, PT, Generator induksi, PBO

Abstract

Small and medium-scale plants connected to the distribution line form a distributed generation (DG) system. Unsynchronized reclosing, due to the operation of a recloser, is an important issue in DG systems. In this paper, simulations of typical DG system are performed to show the effect of unsynchronized reclosing. The simulation results show that unsynchronized reclosing causes the generator to experience over speed, over and under voltage, and over current, which can damage or reduce the life of the generator. A permanent short circuit that causes the contact of recloser to open and close repeatedly has a worse effect than a temporary short circuit. Opening the circuit breaker at point of common coupling with the installation of dummy load can reduce the bad effect of unsynchronized reclosing.

References

C. P. Ion, C. Marinescu , “Autonomous Micro-grid based on Micro hydro Power Plants”, International Conference on Optimization of Electrical and Electronic Equipment (OPTIM) 13th, 24-26 May 2012, Brasov, pp. 941 – 946.

Sumedha Rajakaruna and Naing Naing Maw, “Unregulated Performance of an Induction Generator in an Isolated Micro Hydro Power Plant”, International Power Engineering Conference, IPEC 2005. Nov. 29 -Dec. 2 2005, Singapore.

Duyar, A, Artesis Turkey, Gebze, Kuzkaya, C, Duyar, K., Magureanu, R., “Monitoring and Diagnosis for Induction Microhydro Electric Generators”, IEEE International Symposium on Diagnostics for Electric Machines, Power Electronics and Drives, SDEMPED., 6-8 Sept. 2007, Cracow, pp 399 – 404.

Gorwski, D.A., Wiśniewski, J, Koczara, K., “Grid connection transients of small hydropower generator”, International Conference on Renewable Energies and Power Quality (ICREPQ’12) Santiago de Compostela (Spain), 28th to 30th March, 2012.

Bakhsh, F.I., Islam, S., Ahmad, S., “Simulation for Performance Analysis of Grid-Connected Induction Generators with Input Voltage Control”, Third International Conference on Advanced Computing and Communication Technologies (ACCT), 2013.

Filho, A.F.F., Nascimento, C.S.C., “A method to determine the capacitance required by the operation of a grid-connected induction generator”, International Conference on Electrical Machines (ICEM) XIX, 2010.

Pal, M., Sandhu, K.S., “Behavior of grid connected induction generator due to load disturbances across power network”, Students Conference on Engineering and Systems (SCES), 2014.

Farrag, M. E. A., Putrus, G. A., “Analysis of the Dynamic Performance of Self-Excited Induction Generators Employed in Renewable Energy Generation” www.mdpi.com/journal/energies, ISSN 1996-1073, Energies 2014, 7, 278-294, doi:10.3390/en7010278, 2014.

IEEE Power Engineering Society, “IEEE Std C37.100-1992S, IEEE Standard Definitions for Power Switchgear”, Edition 2.0, 2012.

Anderson, P. M., “Power System Protection”, The IEEE, Inc. New York, 1999, hal. 224.

Rao, S., “EHAV-AC, HVDC Transmission and Distribution Engineering”, Edisi k3-3, Khanna Publisher, Delhi, 1999, hal. 1269.

IEEE Power Engineering Society, “IEEE Std 1547 2003 IEEE Standard for Interconnecting Distributed Resources with Electric power Systems”.

Published
2017-11-29
How to Cite
M. Isnaeni B. S., F. Danang Wijaya, & Eka Firmansyah. (2017). Pengaruh Penutupan-Balik Tak-Sinkron terhadap Generator Induksi 3-Fase dalam Skema Pembangkitan Tersebar. Jurnal Nasional Teknik Elektro Dan Teknologi Informasi, 6(4), 467-471. Retrieved from https://dev.journal.ugm.ac.id/v3/JNTETI/article/view/2822