Analisis Pengaruh Ketidakseimbangan Beban dan Harmonisa Terhadap Arus Netral Pada Trafo Distribusi 8 Kapasitas 500 KVA di PPSDM Migas Cepu
Riki Khomarudin(1*), Lukman Subekti(2)
(1) Universitas Gadjah Mada
(2) Universitas Gadjah Mada
(*) Corresponding Author
Abstract
Abstract – The distribution transformer 8 at the Cepu Oil and Gas Human Resources Development Center has a capacity of 500 kVA with load connected to the boiler and refinery, where the majority of the load is inductive with 1-phase and 3-phase electric motors. load capacity is not the same and operation is not simultaneously indicated that there is an unbalanced load in the line, which can cause a current on the neutral side of the line. Inductive loads supplied, it can also cause a harmonic effect because these loads are non-linear. This study aims to determine the value of the current in the neutral channel and the harmonic content contained in the distribution system due to the installed system usage and load. The case study carried out is using the measurement method using Tang Ampere and Fluke 435, and analysis using vector addition for the calculation of the sum of Neutral Currents in the Distribution Transformer. The results of measurement and analysis of the calculation of the vector addition obtained that the current on the neutral channel side, and the value of the harmonic content on the distribution channel still meets the IEEE 519-2014 standards.
Keywords : Harmonics, neutral currents, THD currents, Unbalanced loads.
Intisari – Trafo distribusi 8 di Pusat Pengembangan Sumber Daya Manusia Minyak dan gas Cepu memiliki kapasitas 500 kVA dengan terhubung beban ke boiler dan kilang, dimana mayoritas beban bersifat induktif dengan motor listrik 1 fasa dan 3 fasa. Kapasitas beban yang tidak sama dan pengoperasian yang tidak bersamaan diindikasi adanya beban yang tidak seimbang didalam saluran, sehingga dapat menimbulkan arus di sisi saluran netral. Beban-beban induktif yang di supplai juga dapat menimbulkan pengaruh harmonisa akibat beban-beban tersebut non linier. Penelitian ini bertujuan untuk mengetahui besar nilai arus pada saluran netral dan kandungan harmonisa yang terdapat pada sistem distribusi akibat sistem penggunaan dan beban yang terpasang. Studi kasus yang dilakukan yakni menggunakan metode pengukuran menggunakan Tang Ampere, dan Fluke 435, serta analisis menggunakan penjumlahan vektor untuk perhitungan penjumlahan Arus Netral pada Trafo Distribusi. Hasil pengukuran dan analisis perhitungan penjumlahan vektor didapat arus disisi saluran netral, serta nilai kandungan harmonisa pada saluran Distribusi masih memenuhi standar IEEE 519-2014.
Kata kunci : Harmonisa, arus netral, THD arus, Ketidakseimbangan Beban.
Full Text:
PDFReferences
[1] Cheng,John. (1996). IEEE Standart 519-2014 (Compliances, Updates, Solutions, and Case Studies). Schneider Electric : Halaman 26 dan Halaman 28.
[2] F.Abidin,Janny. (2013). Evaluasi Nilai Total Harmonic Distortion (THD) pada Transformator di Jaringan Distribusi (studi di Feeder GJN 6 GI Gejayan). Seminar Nasional Ke-8.Sekolah Tinggi Teknologi Nasional Yogyakarta.
[3] JR Stevenson, D William, diterjemahkan oleh : Idris,Kamal Ir.(1984). Analisis
[4] Sistem Tenaga Listrik. Jakarta Pusat : Erlangga
[5] Kabelindo,Datasheet. (2010). Kabelindo NYFGBY Datasheet. PT Kabelindo Murni Tbk.
[6] McGraw-Hill.Copyrighted Material By : Dugan, Roger D.McGranaghan,Mark F. Santosa.Surya, Beaty.H. Wayne. (2004). Electrical Power System Quality.Downloaded from Digital Engineering Library
[7] Setiadji, Julius Sentosa; Machmudsyah, Tabrani; Cipta Wijaya, Yohanes. 2006. Pengaruh Harmonisa Pada Gardu Trafo Tiang Daya 100 kVA di PLN APJ Surabaya Selatan. Universitas Kristen Petra.
[8] Setiadji, Julius Sentosa; Machmudsyah, Tabrani; Isnanto, Yanuar. (2006). Pengaruh Ketidakseibangan Beban Terhadap Arus Netral dan Losses pada Trafo Distribusi. Universitas Kristen Petra.
[9] Repository unila, http://digilib.unila.ac.id/5705/14/BAB%20II.pdf, diakses tanggal 23 April 2018
DOI: https://doi.org/10.22146/juliet.v1i2.59560
Article Metrics
Abstract views : 3939 | views : 6841Refbacks
- There are currently no refbacks.
SINTA 4 accredited based on Decree of the Minister of Research, Technology and Higher Education, Republic of Indonesia Number 225/E/KPT/2022, Vol. 2 No. 1 (2020) - Vol. 6 No. 1 (2025)
e-ISSN: 2746-2536